The GG-H2S-EXP is intended for horn/ strobe and ventilation activation, and is also useful for alarm outputs such as phone dialers and other alarm functions.
The GG-H2S-EXP is designed for detection of hydrogen sulfide vapors in hazardous areas. The standard detection range of 0-50 ppm provides real-time continuous monitoring of concentrations accurately down to 5 ppm with no false alarms.
The GG-H2S-EXP utilizes a proven hydrogen sulfide specifc electrochemical sensor for detecting poisonous H2S gas concentrations. No false alarms due to cross-sensitivities from other gases, and no false alarms from temperature or humidity fluctuations.
The GG-H2S-EXP provides an industry standard linear 4/20 mA output signal proportional to ppm concentration of hydrogen sulfide. Long sensor life with minimal span adjustment can be expected in most applications. The sensor is designed for simple calibration and the sensor head is easily field replaceable.
Features:
Weight | 4.300000 |
---|---|
Condition | New |
Manufacturer | Calibration Technologies (CTI) |
Accuracy | +/-5% of value, but dependant on calibration gas accuracy and time since last calibration |
Detection | Electrochemical (diffusion method) |
Refrigerant Gases | H2S (Hydrogen Sulfide) |
Signal Output | Linear 4/20 mA (max input impedance: 700 Ohms) |
Size | 7.5" high x 6.5" wide x 3.75" deep |
Temperature Range | -40°F to +120°F (-40°C to +49°C) |
Power | 24VDC @ 350mA |
PPM Range | 0-50ppm |
Warranty | 2-years (including sensor element) |
Wiring Connection | 3 conductor, shielded, stranded, 20 AWG cable (General Cable C2525A or equivalent) up to 1500 ft |