The A4A inlet family of regulators are compact, heavy duty, pilot operated, and have remarkable functionality. They sue upstream pressure for the opening force and require a minimum 0.14bar (2psig) pressure drop to open. These valves are normally ordered with close coupled upstream strainers to prevent the entrance of foreign materials into the valve and rest of system. The valve's purpose is to modulate flow of refrigerant gas or liquid to maintain constant upstream pressure as set-for, despite load fluctuations.
Features and Benefits:
Pilot operated characterized Modulating Plug for precise control
Suitable for all common refrigerants and oil
27.6bar (400psig) design pressure (MRP)
Flanges threaded or welded steel pipe and copper tube (copper not for ammonia)
Interchangeable parts
Easy to service
Close coupled strainers, optional
Many control variations are possible with the use of a few Modules and Kits
Stainless Steel Diaphragm
Chrome Plated Pilot Seat
Manual Opening Stem
More Information
More Information
Weight
7.570000
Manufacturer
Parker RS - Refrigerating Specialties
Condition
New
Port Size
3"
Pressure Range PSI
20" Hg to 120 psig
Capacity Range
Full Capacity
Flange Size
No Flanges
Pressure Set Point
15 psi
Reviews
Product Questions